Security News

US water utilities are being breached through unmanaged modems and default passwords, not just software bugs

The Register · 26 Nov 2026
Key Takeaway Before chasing patches, list every internet-connected device (including ones installed by contractors) and make sure none use default passwords or sit exposed without multifactor authentication.

A new study of 236 technology vendors that supply US drinking water, wastewater and industrial water systems suggests the sector's exposure is larger than public records show. The Water Supply Chain Watch index, published by exposure management firm Securin, found almost twice as many vulnerabilities as public records identified. That included 20 exploited flaws missing from the US government's Known Exploited Vulnerabilities (KEV) catalog.

Federal water advisories reached their highest level this year since 2020. Five vendors (Rockwell Automation, Advantech, Schneider Electric, Siemens and ABB) account for 191 of 376 water-tagged advisories. Yet the researchers note that advisory volume does not reliably predict real-world attacks. Advantech had the most critical-rated vulnerabilities, but none of its listed CVEs appear in the KEV catalog. Unitronics had only two water-tagged advisories, yet at least 75 of its controllers were compromised between November 2023 and January 2024 through default or missing passwords.

The report points to the same gap in the July intrusions, which researchers suspect were the work of Iran-linked attackers. They targeted more than 100 water systems across at least 12 states and involved poorly secured internet-connected controllers. As of 17 November, 791 Rockwell MicroLogix 1400 controllers were exposed to the internet. Forescout research cited in the report found that seven in 10 exposed Rockwell controllers in the US sit on mobile carrier networks, where poorly secured cellular modems can give attackers a way in. Those modems are often installed by contractors and frequently go undocumented.

The top recommendation is for utilities to find every cellular modem, including contractor-installed ones, keep them off the open internet, and place a gateway with multifactor authentication in front of them. As Securin's CEO put it, utilities are fixing the vulnerabilities they are told to worry about while attackers get in through equipment nobody knew was connected or passwords nobody changed.

Why it matters

Operators of industrial systems that prioritise work by CVE counts and advisories may be defending the wrong thing, because the assumption that vulnerability feeds show where attacks come from is broken here. The failing controls are asset inventory and credential hygiene, especially for contractor-installed cellular modems that no one documented. This forces a shift from patch-led prioritisation to finding and locking down exposed devices first.

What to do

  • Find every cellular modem in the environment, including those installed by contractors.
  • Remove controllers and modems from direct exposure to the open internet.
  • Put a gateway with multifactor authentication in front of modems and controllers.
  • Change default or missing passwords on all controllers, and watch for inbound traffic on ports 44818, 2222, 102, 502 and 22.
water utilities operational technology critical infrastructure default passwords Iran-linked threat actors
Running SCADA or OT networks? SCADA network segmentation, with a design review checklist ->

Summarised by CISO AI from The Register, written with Claude Sonnet 5.5. We link back to every original so you can read it yourself.