Six Danfoss Fridge Controller Flaws Found in an Hour: Researcher Says Remove Internet Exposure Now

The Register · 17 Nov 2026
Key Takeaway If your business runs refrigeration or other building controllers, make sure none are reachable directly from the internet, and ask your supplier or installer to confirm this.

Carlo Meijer of consultancy Midnight Blue says he found six previously unknown vulnerabilities in the firmware of Danfoss refrigeration controllers in under an hour. He examined version 5.3.2 of the AK-SM800A firmware by hand, without AI tools. The Centre for Cybersecurity Belgium (CCB) warns the flaws could let attackers take control without credentials, keep access after a reset, or disable the controllers altogether.

Meijer says he looked at places where the firmware uses strcpy(), a function that does not check whether the destination has enough space. Vendor code leans on it heavily, and he quickly found five cases where a single one-line web request could crash the device. He argues that turning such a crash into remote code execution is straightforward, noting the affected application runs as root and the firmware lacks common protections such as stack canaries and position-independent executables. A sixth flaw affects the pre-authentication stage and, he says, can be developed into code execution with some extra effort.

Later firmware adds a feature called session control, whose strict setting blocks unauthenticated access to most web interfaces. Meijer found a memory corruption flaw in that protective layer too. He also says the controllers do not use their processor's secure boot features, so an attacker could plausibly stay on a device after a reset, or wipe it or push a bad firmware update to leave it permanently unusable.

Meijer says Danfoss's advice after recent attacks on European supermarkets and blood banks (rotating credentials, applying patches, enabling strict session control) is not enough given the flaws in the code. He recommends removing internet exposure as soon as possible rather than spending scarce resources on piecemeal patching. The CCB also urges removing direct internet exposure, but adds that patches should be applied when available. Danfoss did not respond to The Register's request for comment.

Why it matters

The strict session control setting, which the vendor presented as a mitigation, is itself reported to contain a memory corruption flaw, so following the vendor's hardening advice does not remove the risk. Operators of cold storage, supermarkets and food or medical suppliers who assumed that credential rotation and patching would be enough now face a decision: treat network exposure, not firmware version, as the primary control. Missing secure boot also means a compromised unit may not be cleaned by a reset, so recovery could mean replacement.

What to do

  • Remove direct internet exposure from Danfoss AK-SM800A and similar refrigeration controllers as soon as possible.
  • Apply Danfoss patches when they become available, as the CCB recommends.
  • Rotate credentials and enable strict session control, while recognising these steps alone are not sufficient.
  • Check whether controllers are running firmware version 5.3.2 or later and treat them as affected.
Danfoss ICS security zero-day memory corruption critical infrastructure IoT
Running SCADA or OT networks? SCADA network segmentation, with a design review checklist ->

Summarised by CISO AI from The Register, written with Claude Sonnet 5.5. We link back to every original so you can read it yourself.